SitePro®
Uninterruptible Power Supply (UPS) The GE SitePro family
of high-performance UPS systems provides critical power protection
for a range of applications. All SitePro models operate in
a double conversion mode (providing true on-line operation),
thus providing the highest levels of power reliability. Each
UPS is fully compliant with international standards regarding
Voltage Frequency Independent (VFI) operation. True VFI technology
makes the GE SitePro an extremely reliable UPS for data security
and other demanding critical applications.
This continuous on-line UPS is available in models from 10
kVA up to 500 kVA. For high-power redundant applications,
the GE SitePro can be installed with up to eight units in
parallel, achieving power protection up to 4 MVA. They systems
are controlled in a true peer-to-peer configuration with redundancy
in all critical elements and functions utilizing GE Digital
Energy's exclusive Redundant Parallel Architecture"(RPA")
technology. This advanced technology provides the highest
possible system reliability for mission critical applications
without single points of failure.
The GE SitePro family is supported by world-class training,
power quality applications support, and 24 x 7 global services.
FEATURES & BENEFITS
- High output power factor eliminates need for UPS
oversizing
- Constant high efficiency at full and partial load
- Superior Battery Management (SBM) to enhance battery
life and to prevent battery failure.
- Extremely low output distortion even at non-linear
loads.
- Best in class for variable load applications
- Highest levels of reliability and flexibility with
Redundant Parallel Architecture" (RPA")
- Various operation models: double conversion; voltage
and frequency stabilizer; frequency converter; Intelligent
Energy Management"(IEM")
- Galvanic isolation which provides additional critical
power protection
- UPS monitoring and protection software
|
APPLICATIONS
- Computer and data centers
- Call centers
- Manufacturing and process control units
- Medical equipment and healthcare facilities
- Broadcast and satellite transmission systems
- Transport systems
- Fixed and mobile voice and data transmission systems
- Emergency lighting systems
- Security systems
- Financial systems and services
|
Technical Specifications-CE approved
Topology - True on-line, double conversion (VFI) with
integral static switch and integral service bypass
Technology - Advanced IGBT with SVM strategy, micorprocessor
controlled at optimal switching frequency
Operating Modes - True on-line double conversion, IEM™
for RPA™, voltage and frequency converter, RPA up to
eight units
| Output Power Rating kVA |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
150 |
200 |
250 |
300 |
400 |
500 |
| Output Power Factor |
1 |
1 |
1 |
1 |
1 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
0.9 |
| Output Power Rating kW |
10 |
15 |
20 |
30 |
40 |
54 |
72 |
90 |
108 |
135 |
180 |
225 |
270 |
360 |
450 |
| Dimensions WxDxH (mm) |
680x800x1450 |
750x800x1450 |
110x800x1450 |
110x800x1800 |
1550x800x1800 |
2600x800x1800 |
| Weight (without batteries) kg |
240 |
290 |
290 |
230 |
350 |
475 |
670 |
745 |
750 |
930 |
1000 |
1450 |
1550 |
2725 |
2950 |
| Noise Level (DIN45630) dB(A) |
48 |
50 |
50 |
50 |
55 |
60 |
60 |
63 |
63 |
63 |
65 |
65 |
68 |
68 |
70 |
| Input voltage |
2x380-400-415V + N |
| Input frequency |
50/60Hz +/-10% |
| Output voltage (sinusoidal) |
3x380-400-415V + N |
| Output frequency |
50/60Hz |
| Output distortion at linear load |
<2% |
| Output distortion at non-linear load |
<3% |
| Crest factor |
>3:1 |
| Overload capability on inverter |
125% 10 min., 150% 1 min. (400-500 kVA 30 sec.) |
Output voltage regulation
-static
-dynamic |
+/-1%
+/- 3% |
Overall efficiency at 100% load
(double conversion mode) |
up to 94.5% |
Overall efficiency at 100% load
(IEM mode for single units)* |
up to 97% |
| Ambient operating temperature |
0-40 degrees C (32degrees-104degreesF) |
| Color |
RAL 9010 (white) |
| Protection degree |
IP20 |
| EMC standards |
EN 50091-2/IEC 62040-2 |
| Standard Interfaces |
RS232; alarm contacts; programmable relays |
Specifications subject to change without notice. *10-40kVA
power range only
Technical Specifications-UL approved
Topology - True on-line, double conversion (VFI) with
integral static switch and integral service bypass
Technology - Advanced IGBT with SVM strategy, micorprocessor
controlled at optimal switching frequency
Operating Modes - True on-line double conversion, IEM™
for RPA™, voltage and frequency converter, RPA up to
eight units
Output Power Rating kVA
(at PF=0.60-0.9 lag) |
10 |
15 |
20 |
30 |
40 |
60 |
80 |
100 |
120 |
150 |
200 |
250 |
300 |
400** |
500** |
| Output Power Rating kW |
10 |
15 |
20 |
30 |
36 |
54 |
72 |
90 |
108 |
135 |
180 |
225 |
270 |
360 |
450 |
| Dimensions WxDxH (inches) |
27x32x57 |
29x32x57 |
43x32x57 |
43x32x57 |
61x32x71 |
102x32x71 |
| Weight (lbs) |
816 |
1.014 |
1.080 |
1.245 |
1.411 |
1.047 |
1.654 |
1.841 |
1.896 |
2.040 |
2.194 |
3.197 |
3.417 |
5.593 |
6.393 |
| Noise Level dB(A) |
48 |
50 |
50 |
55 |
60 |
60 |
63 |
63 |
63 |
65 |
65 |
68 |
68 |
70 |
70 |
| Input voltage |
3x208/120 + Neutral |
3x480/277 + Neutral |
| Input frequency |
60/50 Hz +/-10% |
| Output voltage |
3x208/120 + Neutral |
3x480/277 + Neutral |
| Output frequency |
60/50 Hz |
| Output distortion at liner load |
<2% |
| Output distortion at non-linear load |
<3% |
| Overload capability on inverter |
125% 10 min., 150% 1 min. |
Overall efficiency at 100% load
(double conversion mode) |
up to 90% |
up to 93% |
up to 94.5% at 50% load, up to 92.9% at 100% load |
| Immunity and RFI Protection |
EN 50091-2/IEC 62040-2 |
|
Standard Connectivity
|
RS232;
alarm contacts; programmable relays (SNMP optional)
|
Crest factor, output voltage regulation, color, and protection
degree are the same as specified for the CE models.
Specifications subject to change without notice.
|